KL3204 | Bus Terminal, 4-channel analog input, temperature, RTD (Pt100), 16 bit
Sensor types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1.2/5 kΩ)
Connection method 2-wire
Measuring range -200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors)
Conversion time ~ 250 ms
Measuring current typ. 0.5 mA
Resolution 0.1 °C per digit
Measurement error/ uncertainty < ±1 °C